Automatic Tool Changer - Roland udk20 Manual

Double sheet detector
Hide thumbs Also See for udk20:
Table of Contents

Advertisement

B0048991 / Rev. 1.3
4.4

Automatic tool changer

The Roland sensors can be used within an ATC concept (Automatic tool change).
The only requirements we have established are:
Every sensor signal must have its own contact.
The contacts must be low resistive (only gold contacts!).
The contacts must be suited for peak currents of 2 ampere.
The shielding of the cable must not be interrupted and therefore have its own contact.
The contacts must be protected from contamination.
Do not route the cable together with other cables leading high currents.
Die metallic parts of the tooling have to be grounded.
It is not allowed to open the connector during the measuring operation.
After each tool change it is required to perform a zero set command.
.