3.1.3 Verifying the Site Provides for Recommended Air Flow Clearances

150 mm
(6 in.)
3-4
Be sure there is adequate clearance for air ventilation around the drive. For best air
movement, do not mount GV3000/SE drives directly above each other. Note that no
devices are to be mounted behind the drive. This area must be kept clear of all
control and power wiring. Refer to figure 3.2 for recommended air flow clearances.
150 mm (6 in.)
<1
150 mm (6 in.)
<1

Figure 3.2 - Recommended Air Flow Clearances

When installing a GV3000/SE drive, prepare an opening for its ventilating duct at
the top of the cabinet and, if necessary, provide an extension of the duct to connect
between the opening and the duct.
150 mm
(6 in.)
1> IF ADJACENT TO OTHER DRIVES,
THIS CLEARANCE MUST BE
250 MM (10 IN.).
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04