ATTENTION: Do not route signal and control wiring with power wiring
in the same conduit. This can cause interference with drive operation.
!
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
ATTENTION: Unused wires in conduit must be grounded at both ends
to avoid a possible shock hazard caused by induced voltages. Also, if
a drive sharing a conduit is being serviced or installed, all drives using
this conduit should be disabled to eliminate the possible shock hazard
from cross-coupled motor leads. Failure to observe these precautions
could result in bodily injury.
Step 2. Connect the three-phase AC output power motor leads to terminals U/T1,
V/T2, W/T3. See Figure 4.1 for the locations of the terminals.
Step 3. Tighten the three-phase AC output power terminals to 9.8-11.9
Newton-meters (87-104 lb-in) for 30-100 HP drives.