Reliance electric GV3000/SE Installation Manual page 62

30 - 100 hp, 230v ac
Table of Contents

Advertisement

Terminal
Number
16
+24 VDC Power Supply
17
Digital Input 8
(Default - Remote/Local)
ATTENTION: If a maintained start contact is used when the control source = rE, switching from local to
remote from the terminal strip will cause power to be applied to the motor if the remote start contact is
!
closed. Stay clear of rotating machinery in this case. Failure to
observe this precaution could result in bodily injury.
7-12
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring a Remote/Local Input
Parameters/Wiring Connections
Current limited for remote input logic use only.
Digital input 8 is control function programmable through
parameter P.007.
The following parameters must be set:
P.000: Control Source (Only active when P.000 = rE)
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects and assigns
a control function to digital inputs 6 to 8).
P.008: Terminal Strip Speed Reference Source
(Analog, Motor Operated Potentiometer (MOP), or Preset
Speeds)
Note that based on the settings of parameters P.000, P.007, P.008,
and r.030 if an RMI board is used, the following parameters can
affect digital input 8.
P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1-8
Refer to the GV3000/SE Software Start-Up and Reference manual
for additional information.
16
REMOTE
LOCAL
Terminal 17 On = Local Control
Diagram shows factory setting.
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
17