Determining Total Area Required Based On Drive Dimensions; Table 3.1 - Ambient Conditions; Table 3.2 - Drive Dimensions And Weights - Reliance electric GV3000/SE Installation Manual

30 - 100 hp, 230v ac
Table of Contents

Advertisement

3.1.2 Determining Total Area Required Based on Drive Dimensions

GV3000/SE
Drive
Dim. H1
30V2060
544 mm
50V2060
21.4"
60V2060
714 mm
100V2060
28.1"
GV3000/SE
Drive
Dim. A1
30V2060
10 mm
50V2060
0.4"
60V2060
10 mm
100V2060
0.4"
3-2
Be sure that drives are away from oil, coolants, or other airborne contaminants.
Do not install the drive above 1000 meters (3300 feet) without derating output
power. For every 91.4 meters (300 feet) above 1000 meters (3300 feet), derate
the output current 1%.
Verify that the drive location will meet the environmental conditions specified in
table 3.1.
Condition
Operating Temperature (Ambient)
Storage Temperature (Ambient)
Humidity
Drive dimensions and weights are listed in table 3.2. Overall drive dimensions are
illustrated in figure 3.1 as an aid in calculating the total area required by the
GV3000/SE drives.

Table 3.2 - Drive Dimensions and Weights

Dim. H2
Dim. H3
564 mm
504 mm
22.2"
19.8"
734 mm
674 mm
28.9"
26.5"
Dim. A2
Dim. A3
Dim. A4
30 mm
10 mm
30 mm
1.2"
0.4"
1.2"
30 mm
10 mm
30 mm
1.2"
0.4"
1.2"

Table 3.1 - Ambient Conditions

0° to 55°C (32° to 131°F)
–40° to +65°C (–40° to +149°F)
5 to 95% (non-condensing)
Dim. H4
606 mm
235 mm
23.9"
776 mm
245 mm
30.6"
Dim. B1
Dim. B2
51 mm
51 mm
2.0"
2.0"
51 mm
51 mm
2.0"
2.0"
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Specification
Dim. W
Dim. D
354 mm
9.3"
13.6"
366 mm
9.6"
14.4"
Dim. C3
Dim. C1
Dim. C2
9 mm
100 mm
100 mm
0.35"
3.9"
3.9"
200 mm
200 mm
9 mm
7.9"
7.9"
0.35"
Weight
34 kg
75 lbs
44 kg
97 lbs
Dia. d
9 mm
0.35"
9 mm
0.35"

Advertisement

Table of Contents
loading

Table of Contents