Reliance electric GV3000/SE Installation Manual page 67

30 - 100 hp, 230v ac
Table of Contents

Advertisement

Terminal
Number
28
Normally-Closed Contact
(Form B)
29
Normally-Closed Contact
Common (Form B)
30
Normally-Open Contact
(Form A)
31
Normally-Open Contact
Common (Form A)
Wiring the Regulator Board Terminal Strip
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring the Output Status Relays
Both Form A and Form B contacts are rated for 250 VAC/30 VDC at
5 amps resistive or 2 amps inductive load.
The following parameter must be set:
P.013: Output Relay Configuration
Note that depending on the setting of parameter P.013, the
relay coil will energize (the normally-open contact will close and the
normally-closed contact will open). Refer to the GV3000/SE
Software Start-Up and Reference manual for more information.
Parameters/Wiring Connections
N.C.
N.O.
COM
COM
28 29 30 31
USER SUPPLIED
DEVICE
PARAMETER P.013 SELECTS OUTPUT
INDICATION
7-17