Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring a Forward/Reverse Input
Parameters/Wiring Connections
Digital input 6 is control function programmable through
parameter P.007. The following parameters must be set:
P.000: Control Source
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8).
P.008: Terminal Strip Speed Reference Source (Analog,
Motor Operated Potentiometer (MOP), or Preset
Speeds)
P.027: Forward/Reverse Configuration
Note that based on the settings of parameters P.000, P.007, P.008,
and r.030 if an RMI board is used, the following
parameters can affect digital input 6.
P.023: MOP Accel/Decel Time
P.024: MOP Preset Configuration
P.031 to P.038: Preset Speeds 1-8
Refer to the GV3000/SE Software Start-Up and Reference manual
for additional information.
16
FWD
REV
IF P.027 = 1,
FORWARD DIRECTION ONLY
Terminal 19 On = Reverse Direction
Diagram shows factory setting. From the encoder end of
the motor, clockwise rotation indicates forward motor
movement.
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04