Verifying The Site Provides For Recommended Air Flow Clearances; Figure 3.2 - Dimensions For 43 Amp Drives; Table 3.3 - Dimensions And Weight For 43 Amp Drives; Table 3.4 - Recommended Air Flow Clearances - Reliance electric GV3000/SE Hardware Reference, Installation, And Troubleshooting Manual

Bookshelf drive
Hide thumbs Also See for GV3000/SE:
Table of Contents

Advertisement

U.S.
European
Model
Stock
Number
Number
430ER40xx
896.11.12
430ET40xx
896.11.32

3.1.3 Verifying the Site Provides for Recommended Air Flow Clearances

3-4
Table 3.3 – Dimensions and Weight for 43 Amp Drives
Physical Dimensions in mm (in)
Width Dim A
Height Dim B
mm (in)
mm (in)
214 (8.42 )
374 (14.72)
Ø 1 4
D
Front View
Be sure there is adequate clearance for air circulation around the drive. For best air
movement, do not mount GV3000/SE Bookshelf drives directly above each other.
Note that no devices are to be mounted behind the drive. This area must be kept clear
of all control and power wiring.
When mounting the drive within a cabinet, maintain the minimum clearances shown in
table 3.4 to allow adequate air circulation around and through the drive.
Above and below the Bookshelf drive
Between the Bookshelf drive and side cabinet
walls
Between Bookshelf drives
Between other larger drives or heat-producing
devices
Width Dim C
Height Dim D
mm (in)
150 (5.90)
C
A
Figure 3.2 – Dimensions for 43 Amp Drives
Table 3.4 – Recommended Air Flow Clearances
GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06
Mounting
Depth Dim E
mm (in)
mm (in)
422 (16.61)
200 (7.87)
E
Side View
Minimum Clearance
100 mm
20 mm
5 mm
40 mm
Weight
kg
lb
16.5
36
B
4 in
.75 in
.25 in
1.5 in