Table 7.1 - Rs-232 Connections (Terminals 1-3); Table 7.2 - Encoder Connections (Terminals 4-9) - Reliance electric GV3000/SE Installation Manual

30 - 100 hp, 230v ac
Table of Contents

Advertisement

Wiring the Regulator Board Terminal Strip
This chapter describes how to wire the Regulator board terminal strip for stop,
encoder feedback, and remote control signals.
The signals available through the terminal strip are shown in tables 7.1 to 7.7 and
figures 7.1 and 7.2. Table 7.8 provides additional information.
Note that when the Control Source parameter (P.000) is set to remote (rE), the drive
will be controlled by the signals connected to the terminal strip. Refer to the
GV3000/SE Software Start-Up and Reference manual for more information on how
parameter P.000 is used to specify where the drive is controlled from.
Table 7.1 – RS-232 Connections (Terminals 1-3)
Terminal #
1
Transmit (Tx)
2
Receive (Rx)
Regulator Common
3
Notes: The RS-232 terminals should only be used when the RS-232 communication port
(J8) or an Operator Interface Module (OIM) are not being used, as all three devices use
the same transmit/receive lines.
Table 7.2 – Encoder Connections (Terminals 4-9)
Terminal #
+15 VDC
4
Phase A
5
Phase A Not
6
Phase B
7
8
Phase B Not
9
Regulator Common
Notes: An encoder feedback device must be installed if FVC regulation is used.
C
HAPTER
Wiring the Regulator Board
Signal
Signal
7
Terminal Strip
7-1