Reliance electric GV3000/SE Installation Manual page 66

30 - 100 hp, 230v ac
Table of Contents

Advertisement

Terminal
Number
22
Digital Input 3
(Reset)
23
Digital Input 2
(Stop)
24
Digital Input 1
(Start)
25
24 VDC Isolated Common
26
Snubber Resistor Braking
Control Signal
27
+24 VDC Isolated Common
7-16
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring the Reset Input
Wiring the Stop/Start Inputs
Wiring the Snubber Resistor
Parameters/Wiring Connections
The following parameter must be set:
P.000: Control Source
16
Terminal 22 On = Reset
The following parameters must be set:
P.000: Control Source
P.025: Stop Type
16
STOP
Terminal 23 Off = Stop
Terminal 24 On Transition = Start
Used with older Snubber Resistor Braking Kits that require a gate
turn-on signal from the drive (for example, the M/N 2DB2010
series).
Note that terminals 26 and 27 are not to be used with
Snubber Resistor Braking Kits M/N 2SR20400, 2SR20600,
2SR21200, 2SR21800, 2SR20300, and 2SR20450.