Check Motor Rotation; Local-Control Test - GE AF-650 GP Design And Installation Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Start-up and Functional Tes...
Some motors may be unable to run the complete
version of the test. In that case, select [2] Reduced
Auto Tune.
If an output filter is connected to the motor,
select [2] Reduced Auto Tune.
If warnings or alarms occur, see
chapter 10 Warnings and Alarms for resetting the
frequency converter after a trip.
3
3
Run this procedure on a cold motor for best
results.

3.5 Check Motor Rotation

Before running the frequency converter, check the motor
rotation.
1.
Press [Hand].
2.
Press [
3.
Check that the speed shown is positive.
4.
Verity that the wiring between the frequency
converter and the motor is correct.
5.
Verity that the motor running direction matches
the setting in parameter H-48 Clockwise Direction.

3.6 Local-control Test

CAUTION
MOTOR START!
Ensure that the motor, system, and any attached
equipment are ready for start. It is the responsibility of
the user to ensure safe operation under any operational
condition. Failure to ensure that the motor, system, and
any attached equipment are ready for start could result
in personal injury or equipment damage.
32
] for positive speed reference.
When parameter H-48 Clockwise Direction
is set to [0] Normal (default clockwise):
a.
Verify that the motor turns
clockwise.
b.
Verify that the keypad
direction arrow is clockwise.
When parameter H-48 Clockwise Direction
is set to [1] Inverse (counterclockwise):
a.
Verify that the motor turns
counterclockwise.
b.
Verify that the keypad
direction arrow is counter-
clockwise.
NOTICE
The Hand key on the keypad provides a local start
command to the frequency converter. The [Off] key
provides the stop function.
When operating in local mode, the up and down keys on
the keypad increase and decrease the speed output of
the drive. The left and right keys move the display cursor
in the numeric display.
1.
Press [Hand].
2.
Accelerate the frequency converter by pressing
[
decimal point provides quicker input changes.
3.
Note any acceleration problems.
4.
Press [Off].
5.
Note any deceleration problems.
If acceleration problems were encountered:
If warnings or alarms occur, see
chapter 10 Warnings and Alarms
Check that motor data is entered correctly
Increase the ramp time in parameter F-07 Accel
Time 1
Increase current limit in parameter F-43 Current
Limit
Increase torque limit in parameter F-40 Torque
Limiter (Driving)
If deceleration problems were encountered:
If warnings or alarms occur, see
chapter 10 Warnings and Alarms.
Check that motor data is entered correctly.
Increase the ramp time in parameter F-08 Decel
Time 1.
Enable overvoltage control in
parameter B-17 Over-voltage Control.
See chapter 10.4 Warning and Alarm Definitions for resetting
the frequency converter after a trip.
NOTICE
Chapter 3.1 Pre-start through chapter 3.6 Local-control
Test in this chapter conclude the procedures for applying
power to the frequency converter, basic programming,
set-up, and functional testing.
DET-767c All rights reserved.