GE AF-650 GP Design And Installation Manual page 81

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Installation Consideration
To reduce the interference level from the entire system (unit + installation), make motor and brake cables as short as
possible. Avoid placing cables with a sensitive signal level alongside motor and brake cables. Radio interference higher than
50 MHz (airborne) is especially generated by the control electronics.
7.1.2 Emission Requirements
According to the EMC product standard for adjustable speed frequency converters EN/IEC61800-3:2004 the EMC
requirements depend on the intended use of the frequency converter. Four categories are defined in the EMC product
standard. The definitions of the four categories together with the requirements for mains supply voltage conducted
emissions are given in Table 7.1:
Category
Definition
C1
Frequency converters installed in the first environment (home and office) with a
supply voltage less than 1000 V.
C2
Frequency converters installed in the first environment (home and office) with a
supply voltage less than 1000 V, which are neither plug-in nor movable and are
intended to be installed and commissioned by a professional.
C3
Frequency converters installed in the second environment (industrial) with a supply
7
7
voltage lower than 1000 V.
C4
Frequency converters installed in the second environment with a supply voltage
equal to or above 1000 V or rated current equal to or above 400 A or intended for
use in complex systems.
Table 7.1 Categories
When the generic emission standards are used, the frequency converters are required to comply with the limits in Table 7.2:
Environment
First environment
(home and office)
Second environment
(industrial environment)
Table 7.2 Limits
78
Generic standard
EN/IEC61000-6-3 Emission standard for residential, commercial, and
light industrial environments.
EN/IEC61000-6-4 Emission standard for industrial environments.
DET-767c All rights reserved.
Conducted emission requirement
according to the limits given in EN
55011
Class B
Class A Group 1
Class A Group 2
No limit line.
An EMC plan should be made.
Conducted emission requirement
according to the limits given in EN
55011
Class B
Class A Group 1
MG35M402

Advertisement

Table of Contents
loading

Table of Contents