Control Terminal Types - GE AF-650 GP Design And Installation Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Installation
Illustration 2.10 Control Wiring Access for IP55/ Nema 12 and
IP66/Nema 4/4X Indoor

2.5.5.2 Control Terminal Types

Illustration 2.11 shows the removable frequency converter
connectors. Terminal functions and default settings are
summarized in Table 2.5.
Illustration 2.11 Control Terminal Locations
Illustration 2.12 Terminal Numbers
Connector 1 provides four programmable digital
inputs terminals, two extra digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
MG35M402
AF-650 GP™ Design and Installation Guide
See chapter 13.2 General Technical Data for terminal ratings
details.
Terminal
12, 13
18
19
32
33
27
29
20
37
39
42
DET-767c All rights reserved.
optional customer supplied 24 V DC voltage. A
digital input for STO (Safe Torque Off) function.
Connector 2 terminals (+)68 and (-)69 are for an
RS485 serial communications connection.
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output.
Connector 4 is a USB port available for use with
the DCT-10.
Also provided are two Form C relay outputs that
are in various locations depending after the
frequency converter configuration and size.
Some options available for ordering with the unit
may provide extra terminals. See the manual
provided with the equipment option.
Terminal description
Default
Parameter
setting
Digital inputs/outputs
+24 V DC
E-01
[8] Start
E-02
[10] Reversing
E-05
[0] No
operation
E-06
[0] No
operation
E-03
[0] No
operation
E-04
[14] Jog
Safe Torque
Off (STO)
Analog inputs/outputs
AN-50
[0] No
operation
2
Description
24 V DC supply
voltage. Maximum
output current is 200
mA total for all 24 V
loads. Useable for
digital inputs and
external transducers.
Digital inputs.
Selectable for either
digital input or
output. Default setting
is input.
Common for digital
inputs and 0 V
potential for 24 V
supply.
Safe input. Used for
STO.
Common for analog
output.
Programmable analog
output. The analog
signal is 0–20 mA or
4–20 mA at a
maximum of 500 Ω
23
2

Advertisement

Table of Contents
loading