Status Messages

8 Status Messages

8.1 Status Display

When the frequency converter is in Status mode, status
messages are generated automatically and appear in the
bottom line of the display (see Illustration 8.1).
1 Operating mode (see Table 8.1)
2 Reference site (see Table 8.2)
3 Operation status (see Table 8.3)
Illustration 8.1 Status Display

8.2 Status Message Definitions

Table 8.1 to Table 8.3 describe the shown status messages.
Off
The frequency converter does not react to any
control signal until [Auto] or [Hand] is pressed.
Auto
The frequency converter is controlled from the
control terminals and/or the serial communi-
cation.
Hand
Control the unit via the navigation keys on
the keypad. Stop commands, reset, reversing,
DC brake, and other signals applied to the
control terminals can override local control.
Table 8.1 Operating mode
Remote
The speed reference is given from external
signals, serial communication, or internal
preset references.
Local
The frequency converter uses [Hand] control
or reference values from the keypad.
Table 8.2 Reference Site
MG35M402
AF-650 GP™ Design and Installation Guide
AC Brake
Auto Tune finish
OK
Auto Tune ready Auto Tune is ready to start. Press [Hand] to
Auto Tune
running
Coast
Ctrl. Decel
Current High
Current Low
DC Hold
DC Stop
Feedback high
Feedback low
DET-767c All rights reserved.
AC Brake was selected in parameter B-10 Brake
Function. The AC brake over-magnetizes the
motor to achieve a controlled slow down.
Auto Tune was carried out successfully.
start.
Auto Tune process is in progress.
Coast inverse was selected as a function
for a digital input. The corresponding
terminal is not connected.
Coast activated by serial communication
Ctrl. Decel was selected in
parameter SP-10 Line failure.
The mains voltage is below the value set
in parameter SP-11 Line Voltage at Input
Fault at mains fault
The frequency converter ramps down the
motor using a controlled ramp down
The frequency converter output current is
above the limit set in parameter H-71 Warning
Current High.
The frequency converter output current is
below the limit set in parameter H-70 Warning
Current Low
DC hold is selected in parameter H-80 Function
at Stop and a stop command is active. The
motor is held by a DC current set in
parameter B-00 DC Hold Current.
The motor is held with a DC current
(parameter B-01 DC Brake Current) for a
specified time (parameter B-02 DC Braking
Time).
DC brake is activated in parameter B-03 DC
Brake Cut In Speed [RPM] and a stop
command is active.
DC brake (inverse) is selected as a function
for a digital input. The corresponding
terminal is not active.
The DC brake is activated via serial
communication.
The sum of all active feedbacks is above the
feedback limit set in parameter H-77 Warning
Feedback High.
The sum of all active feedbacks is below the
feedback limit set in parameter H-76 Warning
Feedback Low.
8
8
85