Warnings and Alarms
No.
Description
88
Option Detection
89
Mechanical Brake Sliding
90
Feedback Monitor
91
Analog input 54 wrong settings
99
Locked rotor
101
Speed monitor
104
Mixing fans
122
Mot. rotat. unexp.
123
Motor mod. changed
220
Configuration File Version not supported
246
Pwr.card supply
250
New spare parts
251
New Type Code
253
X49/9 Overload
254
X49/11 Overload
255
X49/7 Overload
430
PWM Disabled
Table 10.2 Alarm/Warning Code List
(X) Dependent on parameter
1) Cannot be auto reset via parameter H-04 Auto-Reset (Times)
A trip is the action following an alarm. The trip coasts the
motor and is reset by pressing [Reset] or by a digital input
(parameter group E-1# [1]). The origin event that caused an
alarm cannot damage the frequency converter or cause
dangerous conditions. A trip lock is an action when an
0
10
alarm occurs, which could damage the frequency converter
or connected parts. A trip lock situation can only be reset
by a power cycling.
Bit
Hex
Alarm Word Extended Status Word
0
00000001
1
00000002
2
00000004
3
00000008
4
00000010
5
00000020
6
00000040
7
00000080
100
Warning
(X)
Dec
Alarm Word
Alarm Word 2
1
Brake Check (A28) ServiceTrip,
Read/Write
2
Pwr. Card Temp
ServiceTrip
(A69)
(reserved)
4
Earth Fault (A14)
ServiceTrip,
Typecode/
Sparepart
8
Ctrl.Card Temp
ServiceTrip
(A65)
(reserved)
16
Ctrl. Word TO
ServiceTrip
(A17)
(reserved)
32
Over Current
Reserved
(A13)
64
Torque Limit
Reserved
(A12)
128
Motor Th Over
Reserved
(A11)
DET-767c All rights reserved.
Alarm/Trip
Alarm/Trip Lock
X
(X)
X
X
X
X
X
X
X
X
X
X
X
Warning
Alarm
Trip locked
Table 10.3 LED Indication
Warning Word
Brake Check (W28)
Pwr. Card Temp (W69)
Earth Fault (W14)
Ctrl.Card Temp (W65)
Ctrl. Word TO (W17)
Over Current (W13)
Torque Limit (W12)
Motor Th Over (W11)
Parameter
reference
X
Parameter EC-61 Feedba
ck Signal Monitoring
X
S202
X
X
X
Yellow
Flashing red
Yellow and red
Warning
Extended
Word 2
Status Word
Reserved
Ramping
Reserved
Auto Tune Running
Reserved
Start CW/CCW
Reserved
Slow Down
Catch Up
Reserved
Feedback High
Reserved
Feedback Low
Reserved
Output Current