Specifications
AF-650 GP 3-phase [kW (hp)]
0.75 (1)
1.5 (2)
2.2 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
Table 13.25 525–600 V, IP55/Nema 12 and IP66/Nema 4X
AF-650 GP 3-phase [kW (hp)]
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
132 (200)
160 (250)
200 (300)
250 (350)
315 (400)
355 (500)
400 (550)
500 (650)
560 (750)
630 (900)
710 (1000)
800 (1150)
900 (1250)
1000 (1350)
Table 13.26 525–690 V, IP21/Nema 1 and IP55/Nema 12 and IP66/Nema 4X
MG35M402
AF-650 GP™ Design and Installation Guide
Recommended fuse size
gG-16
gG-35
gG-50
gG-125
aR-250
Recommended fuse size
gG-25
gG-32
gG-40
gG-63
gG-80
gG-100
gG-125
aR-250
aR-315
aR-350
aR-400
aR-500
aR-550
aR-700
aR-900
aR-1600
aR-2000
DET-767c All rights reserved.
Recommended maximum fuse
gG-32
gG-80
gG-100
gG-160
aR-250
Recommended maximum fuse
gG-63
gG-80
gG-100
gG-125
gG-160
aR-250
aR-315
aR-350
aR-400
aR-500
aR-550
aR-700
aR-900
aR-1600
aR-2000