Immunity Requirements - GE AF-650 GP Design And Installation Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Installation Consideration
7.1.3 EMC Test Results (Emission)
The following test results have been obtained using a system with a frequency converter (with options if relevant), a
shielded control cable, a control box with potentiometer, and a motor and motor shielded cable.
RFI filter type
Standard
Class A1/B RFI Filter installed
0.75–45 kW 200–240 V
0.75–90 kW 380–500 V
Class A2 RFI Filter installed
0.75–3.7 kW 200–240 V
5.5–37 kW 200–240 V
0.75–7.5 kW 380–500 V
11–75 kW 380–500 V
90–800 kW 380–500 V
90–1200 kW 525–690 V
No RFI Filter installed
0.75–75 kW 525–600 V
Table 7.3 EMC Test Results (Emission)

7.2 Immunity Requirements

The immunity requirements for frequency converters depend on the environment where they are installed. The
requirements for the industrial environment are higher than the requirements for the home and office environment. All GE
frequency converters comply with the requirements for the industrial environment and therefore comply also with the lower
requirements for home and office environment with a large safety margin.
In order to document immunity against burst transient from electrical phenomena, the following immunity tests have been
made on a system consisting of a frequency converter (with options if relevant), a shielded control cable and a control box
with potentiometer, motor cable, and motor.
The tests were performed in accordance with the following basic standards:
EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges (ESD): Simulation of electrostatic discharges from human
beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic field radiation, amplitude modulated simulation of the
effects of radar and radio communication equipment and mobile communications equipment.
EN 61000-4-4 (IEC 61000-4-4): Burst transients: Simulation of interference brought about by switching a contactor,
relay, or similar devices.
EN 61000-4-5 (IEC 61000-4-5): Surge transients: Simulation of transients brought about for example, by lightning
that strikes near installations.
EN 61000-4-6 (IEC 61000-4-6): RF Common mode: Simulation of the effect from radio-transmission equipment
joined by connection cables.
See Table 7.4.
MG35M402
AF-650 GP™ Design and Installation Guide
Conducted emission
Maximum shielded cable length
Industrial environment
EN 55011
EN 55011
Class A2
Class A1
150 m
150 m
150 m
150 m
5 m
No
25 m
No
5 m
No
25 m
No
150 m
No
150 m
No
DET-767c All rights reserved.
Housing, trades,
Industrial
and light
environment
industries
EN 55011
EN 55011
Class B
Class A1
50 m
Yes
50 m
Yes
No
No
No
No
No
No
No
No
No
No
No
No
Radiated emission
Housing, trades, and
light industries
EN 55011
Class B
No
No
No
No
No
No
No
No
79