1.1.13 Connecting to Mains and Motor

1
The frequency converter is designed to operate all standard three-phased asynchronous motors.
The frequency converter is designed to accept mains/motor cables with a maximum cross-section of 4 mm
2
section 16 mm
/6 AWG (M4 and M5).
Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both the decoupling plate and the motor
metal.
Keep motor cable as short as possible to reduce the noise level and leakage currents.
For further details on mounting of the decoupling plate, please see instruction MI.02.BX.YY.
Also see EMC-Correct Installation in Operating Instruction MG.02.AX.YY.
Step 1: First, mount the earth wires to earth terminal.
Step 2: Connect motor to terminals U, V and W.
Step 3: Mount mains supply to terminals L1/L, L2 and
L3/N (3-phase) or L1/L and L3/N (single-phase) and tighten.
6
2
/10 AWG (M1, M2 and M3) and maximum cross-
Illustration 1.2: Mounting of earth cable, mains and motor wires.