Emerson Oxymitter 5000 Instruction Manual page 201

Oxygen transmitter
Hide thumbs Also See for Oxymitter 5000:
Table of Contents

Advertisement

Instruction Manual
IM-106-350, Rev 2.2
July 2008
Figure D-6. Situation #2
Diagram
Table D-5. Analog Input
Function Diagram for a Pressure
Transmitter used in Level
Measurement (Situation #2)
Situation #2
The transmitter in situation #1 is installed below the tank in a position where
the liquid column in the impulse line, when the tank is empty, is equivalent to
2.0 psi (Figure D-6).
16 ft
0 ft
Solution
Table D-5 lists the appropriate configuration settings.
Parameter
L_TYPE
XD_SCALE
OUT_SCALE
Oxymitter 5000
Empty Tank
2.0 psi measured at
the transmitter
Configured Values
Indirect
2 to 9 psi
0 to 16 ft
D-11