Emerson Oxymitter 5000 Instruction Manual page 190

Oxygen transmitter
Hide thumbs Also See for Oxymitter 5000:
Table of Contents

Advertisement

Oxymitter 5000
Table C-5. Channel 1 Status
Alarm Condition
Open Thermocouple
Shorted Thermocouple
Reversed Thermocouple
Heater Open Circuit
High High Heater Temperature
High Case Temperature
Low Heater Temperature
High Heater Temperature
Open Cell Circuit
High AC Impedance / Cell Bad
EEPROM Parameters Corrupt
Calibration Recommended
Invalid Slope Value
Invalid Cell Constant Value
Bad Calibration
In Calibration
During Warm Up
The status of channel 1 is affected by the state of the unit alarm, as shown in Table C-5. In all cases, the channel
will read what it believes is the correct oxygen value. Self-clearing alarms are reset when the alarm condition goes
away. All others require the Oxymitter 5000 to be restarted
C-6
Channel 1 Status
Bad
Bad
Bad
Bad
Bad
Bad
Bad
Bad
Bad
Uncertain
Bad
Good
Uncertain
Uncertain
Uncertain
Uncertain
Bad
Self-clearing?
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
Yes
Instruction Manual
IM-106-350, Rev 2.2
July 2008