Table C-2. IO Pin Mode Values
Code Value
Description
0
No Alarm
1
Unit Alarm
2
Low 02 Alarm
3
Low 02/Unit Alarm
4
Cal Recommended
5
Cal Recommended/Unit Alarm
6
Low 02/Cal Recommended
7
Low 02/Unit/Cal Recommended
8
Cal Recommended->Handshake
9
Handshake
Table C-3. Unit Alarm Values
Value of
Alarm Number
DETAILED_STATUS
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16384
16
32768
17
65536
18
131072
Table C-4. I/O Channel
Configuration
Transducer Block
Channel Value
Process Variable
1
Oxygen
2
Case Temperature
3
Sensor Temperature
Refer to Appendix D for instructions on how to implement these variables.
Value of BLOCK_ALARM
(see FF-903)
0
NONE
1
MECHANICAL_FAILURE
2
MECHANICAL_FAILURE
4
MECHANICAL_FAILURE
8
N/A
16
N/A
32
MECHANICAL_FAILURE
64
MECHANICAL_FAILURE
128
MECHANICAL_FAILURE
256
MECHANICAL_FAILURE
512
MECHANICAL_FAILURE
1024
MECHANICAL_FAILURE
2048
N/A
4096
MECHANICAL_FAILURE
8192
DATA_INTEGRITY_ERROR
N/A
CONFIGURATION_ERROR
CONFIGURATION_ERROR
CONFIGURATION_ERROR
No Alarm Active
Open Thermocouple
Shorted Thermocouple
Reversed Thermocouple
Not a valid alarm
Not a valid alarm
Heater Open Circuit
High High Heater Temperature
High Case Temperature
Low Heater Temperature
High Heater Temperature
Open Cell Circuit
Not a valid alarm
High AC Impedance / Cell Bad
EEPROM Parameters Corrupt
Calibration Recommended
Invalid Slope Value
Invalid Cell Constant Value
Bad Calibration
XD_SCALE Units
%
o
C
o
C
Oxymitter 5000
Description
C-5