FOUNDATION FIELDBUS
O
CAL METHOD
2
To perform a calibration using the FOUNDATION fieldbus use the following
procedure.
1. From the computer running the fieldbus control program, run the O
Method.
Failure to remove the Oxymitter 5000 from automatic control loops prior to performing this
procedure may result in dangerous operating conditions.
2. In the first O
CAL screen, a "Loop should be removed from automatic
2
control" warning appears. Remove the Oxymitter 5000 from any
automatic control loops to avoid a potentially dangerous operating
condition and press OK.
3. From this point follow the on-screen prompts to complete the calibration
procedure. When a step is complete select Proceed to Next Step and
press the Next button.
4. During the wait periods, such as during a purge, the Time Remaining
display may be updated by selecting Update and pressing Next button.
Oxymitter 5000
Cal
2
7-5