Current Derating Depending On The Pulse Frequency, 400 V Inverters - Siemens PM240-2 Hardware Installation Manual

Sinamics g120 built-in unit power module
Table of Contents

Advertisement

Technical data
7.4 Technical data, 400 V inverters
7.4.3

Current derating depending on the pulse frequency, 400 V inverters

Article number
6SL3210-1PE11-8❒L1
6SL3210-1PE12-3❒L1
6SL3211-1PE13-2❒L1
6SL3210-1PE14-3❒L1
6SL3210-1PE16-1❒L1
6SL321❒-1PE18-0❒L1
6SL3210-1PE21-1❒L0
6SL3210-1PE21-4❒L0
6SL321❒-1PE21-8❒L0
6SL3210-1PE22-7❒L0
6SL321❒-1PE23-3❒L0
6SL3210-1PE23-8❒L0
6SL3210-1PE24-5❒L0
6SL3210-1PE26-0❒L0
6SL3210-1PE27-5❒L0
6SL3210-1PE28-8❒L0
6SL3210-1PE31-1❒L0
6SL3210-1PE31-5❒L0
6SL3210-1PE31-8❒L0
6SL3210-1PE32-1❒L0
6SL3210-1PE32-5❒L0
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected
86
LO base load output current for a pulse frequency of ...
2 Khz /
6 kHz
8 kHz
4 kHz
1.7
1.4
1.2
2.2
1,9
1.5
3.1
2.6
2.2
4.1
3.5
2.9
5.9
5
4.1
7.7
6.5
5.4
10.2
8.7
7.1
13.2
11.2
9.2
18
15.3
12.6
26
22.1
18.2
32
27.2
22.4
38
32.3
26.6
45
38.3
31.5
60
51
42
75
63.8
52.5
90
76.5
63
110
93.5
77
145
123.25
108.75
178
151.3
133.5
205
---
---
250
---
---
Hardware Installation Manual, 12/2015, A5E33294624B AD
[A]
10 kHz
12 kHz
14 kHz
1
0.9
0.8
1.3
1.1
1
1,9
1.6
1.4
2.5
2.1
1.8
3.5
3
2.7
4.6
3.9
3.5
6.1
5.1
4.6
7.9
6.6
5.9
10.8
9
8.1
15.6
13
11.7
19.2
16
14.4
22.8
19
17.1
27
22.5
20.3
36
30
27
45
37.5
33.8
54
45
40.5
66
55
49.5
---
---
---
---
---
---
---
---
---
---
---
---
Power Module PM240-2
16 kHz
0.7
0.9
1.2
1.6
2.4
3.1
4.1
5.3
7.2
10.4
12.8
15.2
18
24
30
36
44
---
---
---
---

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents