Table 7- 12
PM240-2, IP20, frame sizes A, 3-phase 380 ... 480 VAC
Article no. - without filter
Article no. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight without filter
Weight with filter
Power Module PM240-2
Hardware Installation Manual, 12/2015, A5E33294624B AD
6SL3210...
...1PE11-8UL1
6SL3210...
...1PE11-8AL1
0.55 kW
2.3 A
1.7 A
0.37 kW
2.0 A
1.3 A
3NA3 804 (4 A)
10 A Class J
0.04 kW
5 l/s
1.3 kg
1.5 kg
7.4 Technical data, 400 V inverters
Branch protection and short-circuit
...1PE12-3UL1
...1PE12-3AL1
0.75 kW
2.9 A
2.2 A
0.55 kW
2.6 A
1.7 A
3NA3 804 (4 A)
10 A Class J
0.04 kW
5 l/s
1.3 kg
1.5 kg
Technical data
...1PE13-2UL1
...1PE13-2AL1
1.1 kW
4.1 A
3.1 A
0.75 kW
3.3 A
2.2 A
3NA3 801 (6 A)
15 A Class J
0.04 kW
5 l/s
1.3 kg
1.5 kg
79