Siemens PM240-2 Hardware Installation Manual page 82

Sinamics g120 built-in unit power module
Table of Contents

Advertisement

Technical data
7.4 Technical data, 400 V inverters
Table 7- 17
PM240-2, IP20, frame sizes C, 3-phase 380 ... 480 VAC
Article no. - without filter
Article no. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight without filter
Weight with filter
Table 7- 18
PM240-2, PT, frame sizes C, 3-phase 380 ... 480 VAC
Article no. - without filter
Article no. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight without filter
Weight with filter
1) approx. 0.3 kW through the heatsink;
82
6SL3210...
...1PE22-7UL0
6SL3210...
...1PE22-7AL0
11.0 kW
32.6 A
26.0 A
7.5 kW
27.0 A
18.0 A
3NE 1817-0 (50 A)
50 A Class J
0.3 kW
18.5 l/s
4.7 kg
5.3 kg
6SL3211...
...1PE23-3UL0
6SL3211...
...1PE23-3AL0
15.0 kW
39.9 A
32.0 A
11.0 kW
36.0 A
26.0 A
3NE 1817-0 (50 A)
50 A Class J
0.37 kW
18.5 l/s
5.8 kg
6.3 kg
...1PE23-3UL0
...1PE23-3AL0
15.0 kW
39.9 A
32.0 A
11.0 kW
36.0 A
26.0 A
3NE 1817-0 (50 A)
50 A Class J
0.37 kW
18.5 l/s
4.8 kg
5.4 kg
1)