Component Specification According To Ul; Permissible Motors - Siemens PM240-2 Hardware Installation Manual

Sinamics g120 built-in unit power module
Table of Contents

Advertisement

Introduction

3.1 Component specification according to UL

3.1
Component specification according to UL
The components of the SINAMICS G120 product family are UL-certified. The certification is
indicated on the products using the UL Listing Mark.
You can find proof of the certification on the Internet UL certificates (http://www.ul.com)
under "Tools / Online Certifications Directory" by entering the file number or the "Name".
The UL file number for the Power Modules of the SINAMICS G120 product family is:
● E121068 for FSA, FSB and FSC
● E192450 for FSD, FSE and FSF
3.2

Permissible motors

Use motors for inverter operation or with higher insulation levels.
Motors for 200 V Power Modules
For the 200 V Power Modules, induction motors are permissible in the range from
25 % ... 150 % of the inverter power without any restrictions.
Motors for 400 V Power Modules
For the 400 V Power Modules, induction motors are permissible in the range from
25 % ... 150 % of the inverter power without any restrictions.
Motors for 690 V Power Modules
For the 690 V Power Modules, induction motors are permissible in the range from 50
% ... 150 % of the inverter power without any restrictions.
20
Hardware Installation Manual, 12/2015, A5E33294624B AD