Technical Data, 400 V Inverters; General Data, 400 V Inverters - Siemens PM240-2 Hardware Installation Manual

Sinamics g120 built-in unit power module
Table of Contents

Advertisement

7.4

Technical data, 400 V inverters

Motors for 400 V Power Modules
For the 400 V Power Modules, induction motors are permissible in the range from
25 % ... 150 % of the inverter power without any restrictions.
Use motors for inverter operation or with higher insulation levels.
7.4.1

General data, 400 V inverters

Property
Line voltage
Output voltage
Input frequency
Output frequency
Line impedance
Power factor λ
Inrush current
Overvoltage category acc.
to EN 60664-1
Pulse frequency
Short-circuit current rating
(SCCR)
Electromagnetic compati-
bility according to IEC/EN
61800-3
Braking methods
Power Module PM240-2
Hardware Installation Manual, 12/2015, A5E33294624B AD
Version
FSA ... FSC
380 V ... 480 V 3-ph. AC ± 10 %
FSD ... FSF
3 AC 380 V ... 480 V -20 %, +10 %
3 AC 0 V ... 0.95 x input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
FSA ... FSC
Uk ≥ 1 %, for lower values, we recommend a line reactor, or a Power Module
with the next higher power rating.
FSD ... FSF
Line reactor not required
FSA ... FSC
0.7 without line reactor for Uk ≥ 1 %
0.85 with line reactor for Uk < 1 %
FSD ... FSF
0.95 line reactor not required
< LO base load input current
The inverter insulation is designed for surge voltages according to overvoltage Category III.
Factory setting
4 kHz for devices with an LO base load power < 75 kW
2 kHz for devices with an LO base load power ≥ 75 kW
Can be adjusted in 2 kHz steps as follows:
2 kHz ... 16 kHz for devices with an LO base load power < 55 kW
2 kHz ... 8 kHz for devices with an LO base load power ≥ 55 kW
If you increase the pulse frequency, the inverter reduces the maximum output current.
FSA ... FSC ≤ 100 kA rms
FSD ... FSF ≤ 65 kA rms
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
Devices with integrated filter are suitable for Category C2 environments.
DC braking, compound braking, dynamic braking with integrated braking chopper
Technical data
7.4 Technical data, 400 V inverters
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents