Technical data
7.4 Technical data, 400 V inverters
Property
Degree of protection ac-
cording to EN 60529
Ambient temperature
Ambient conditions accord-
ing to EN 60721-3-3
Temperature during stor-
age according to EN
60721-3-3
Cooling air
Relative humidity
Pollution according to EN
61800-5-1
Shocks and vibration ac-
cording to EN 60721-3-1
Installation altitude
Approvals
78
Version
Chassis de-
IP20
vices
IP20,
PT devices
IP54
FSA ... FSC:
LO base load power without derating:
HO base load power without derating:
LO/HO base load power with derating:
FSD ... FSF:
LO base load power without derating:
HO base load power without derating:
LO/HO base load power with derating:
Restrictions for special ambient conditions (Page 92)
For the maximum permissible ambient temperature, also observe the permissible ambient
temperatures for the Control Unit and possibly operator panel (IOP or BOP-2) .
FSA ... FSC:
Protected against damaging chemical substance, according to environmental
Class 3C2
FSD ... FSF
Protected against damaging chemical substance, according to environmental
Class 3C3
-40 °C ... +70 °C
clean and dry air
< 95%
suitable for environments with degree of pollution 2, condensation not permissible
Long-term storage in the transport packaging according to Class 1M2
Transport in the transport packaging according to Class 2M3
Vibration in operation according to Class 3M2
without derating:
with derating:
Restrictions for special ambient conditions (Page 92)
FSA ... FSC
cULus, CE, C-tick, KCC
FSD ... FSF
cULus, CE, C-tick, SEMI F47, KCC, WEEE, RoHS, EAC
Must be installed in a control cabinet
Must be installed in a control cabinet
at the control cabinet panel
-10 °C ... +40 °C
-10 °C ... +50 °C
-10 °C ... + 60° C
-20 °C ... +40 °C
-20 °C ... +50 °C
-20 °C ... + 60° C
up to 1000 m above sea level
up to 4000 m above sea level