Cable Cross-Sections And Tightening Torques - Siemens PM240-2 Hardware Installation Manual

Sinamics g120 built-in unit power module
Table of Contents

Advertisement

Technical data

7.2 Cable cross-sections and tightening torques

7.2
Cable cross-sections and tightening torques
Table 7- 1
Connection type, cable cross sections and tightening torques
Inverters
Connection
FSA
Line, motor cable,
DC link and braking
resistor
FSB
Line, motor cable,
DC link and braking
resistor
FSC
Line, motor cable,
DC link and braking
resistor
FSD
Line, motor cable and
DC link
Braking resistor
FSE
Line, motor cable and
DC link
Braking resistor
FSF
Line, motor cable and
DC link with
cable lugs according to
SN71322
Braking resistor
68
Cross-section and tightening torque
Metric
1.5 ... 2.5 mm
0.5 Nm
2
1.5 ... 6 mm
0.6 Nm
2
6 ...16 mm: 1.3 Nm
10 ... 35 mm
: 2.5 ... 4.5 Nm
2
2.5 ... 16 mm
: 1.2 ... 1.5 Nm
2
25 ... 70 mm
: 8 ... 10 Nm
2
10 ... 35 mm
: 2.5 ... 4.5 Nm
2
35 ... 2*120 mm
: 22 ... 25 Nm
2
25 ... 70 mm
: 8 ... 10 Nm
2
Hardware Installation Manual, 12/2015, A5E33294624B AD
Imperial
16 ... 14 AWG: 4.5 lbf in
16 ... 10 AWG: 5.5 lbf in
10 ... 6 AWG: 12 lbf in
20 ... 10 AWG: 22 lbf in
8 ... 2 AWG: 40 lbf in
20 ... 6 AWG: 15 lbf in
6 ... 3/0 AWG: 88.5 lbf in 25 mm
20 ... 10 AWG: 22 lbf in
8 ... 2 AWG: 40 lbf in
1 ... 2*4/0 AWG: 210 lbf.in --
6 ... 3/0 AWG: 88.5 lbf in 25 mm
Power Module PM240-2
Strip
lengths
8 mm
8 mm
10 mm
18 mm
10 mm
18 mm