1MRK511240-UEN B
7.4
670 series
Engineering Manual
Configured IED Description (*.cid) for the IEC 61850 structure as
needed for the IED at runtime.
IED Capability Description (*.icd) for the IEC 61850 structure, see
Figure
57.
IEC08000416 V1 EN
Figure 57:
3.
The SCL Export Options window opens.
4.
Select Export Private Sections, Export As SCL Template or Include Goose
Sending IEDs and click Export, see
IEC08000418 V1 EN
Figure 58:
IEC 61850: Export IED file Options
Engineering of vertical and horizontal
communication in IET600
For IEC 61850 engineering a separate system configuration tool is needed to be
used with PCM600. In PCM600 Ver. 2.3 or earlier the recommended tool is
CCT600. In PCM600 Ver. 2.4 or later the recommended tool is IET600, which is
also included in the PCM600 Engineering Pro installation package.
Procedure for signal engineering for the station by using IET600:
1.
Create a project in IET600.
2.
Import the SCD file exported from PCM600.
All data sets, report control blocks and GOOSE control blocks
must be located at LD0/LLN0. Due to IED capability, there are
limitations regarding the maximum number of data sets,
IEC 61850 communication engineering
IEC 61850: Export IED file type selection
Figure
IEC08000418.vsd
Section 7
IEC08000416.vsd
58.
75

Advertisement

Table of Contents
loading

Table of Contents