ABB Relion 670 series Engineering Manual page 59

Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

1MRK511240-UEN B
670 series
Engineering Manual
Binary
BIM
Input
IOM BI
HMI
LEDs
LEDs
BOM
Binary
Output
IOM BO
Analog
TRM
Input
GOOSE
GOOSE Inputs
Input blocks
Hardware
IO interfaces
(X-direction)
IEC09000709 V1 EN
Figure 36:
SMT: Operation principles
A binary input channel can be connected to one or several function block inputs,
see
Figure
37. If a binary input channel is connected to several different function
blocks in ACT, the connection will appear as glue logic in SMT.
A binary output channel can only be activated from one function block output. If it
should be activated from more than one function block output, glue logic has to be
used. Glue logic means inserting a logical gate (OR and AND blocks) between the
function blocks and the binary output channel. This can be engineered in SMT.
Connections made in SMT will automatically also be shown in
ACT.
Protection and control engineering
FBs
FBs
SMAI
IEC 61850
Goose_Bin
Intl_AP
Signal Matrix
(Y-direction)
Section 5
FBs
IEC09000709.vsd
53