Section 4
Setting up a project
4.6.1
38
Procedure to insert a pre-configuration
1.
Right-click the bay and select Import ... to select the IED template file
(*.pcmi) , see
Figure
IEC09000644 V1 EN
Figure 25:
Import an IED from the context menu
2.
Import the *.pcmi file from the bay level in the plant structure.
3.
Click OK to insert the new IED object in the plant structure.
4.
Modify the configuration in ACT in case of changes.
5.
Write the configuration to the IED.
Ordered default configurations are not locked. The user can use any
of the available default configurations in the IED or as a base for
the own configuration. The only requirement is that all needed
hardware and software options are available.
It is possible to give the inserted IED in the plant structure a user
defined name. Be sure to only user characters a-z, A-Z, 0-9 and _.
Do not use space character in IED names.

Setting IED IP address in the project

There are two alternatives to set IP address of the IED object in PCM600. The IED
object in PCM600 must have the same IP address and subnetwork mask as the
front or rear port on the physical IED to which the PC is connected. The IP address
of the physical IEDs front and rear port can not be set from PCM600 but only from
LHMI.
Via the first window of the wizard when including a new IED in a project, see
Figure
26.
25.
IEC09000644-1-en.vsd
1MRK511240-UEN B
670 series
Engineering Manual