1MRK511240-UEN B
4.6
670 series
Engineering Manual
IEC08000374 V1 EN
Figure 13:
PCM600: IEC 61850 signal designation concept

Inserting an IED

The context menu or the Object Types view shows the available 670 series IEDs
possible to insert, on the bay level in the plant structure, according to the installed
connectivity package.
In the plant structure it is possible to:
Insert an IED in Offline mode or in Online mode:
Online mode: When the IED is already connected to PCM600 and the
communication is established, PCM600 can read the configuration
directly from the physical IED. This is useful when an order specific IED
is used. The order configuration is written to the IED at the factory and
can be accessed by PCM600. The housing type, the used overlay version
for local HMI and the IO boards included in the IED will be read from
the IED directly.
Offline mode: When the physical IED is not available or not connected
to PCM600 the engineering steps are done without any synchronization
Setting up a project
IEC08000374.vsd
Section 4