Exporting Scl Files From Pcm600 - ABB Relion 670 series Engineering Manual

Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

1MRK511240-UEN B
7.3
670 series
Engineering Manual
For more details please refer to the IEC 61850 standards. In the following
description it is assumed that PCM600 together with IET600 is used as system
configuration tool.
A short form of a typical sequence is shown in
is exported as a SCD file.
1.
Export SCL files from PCM600. In the scenario in
Other SCL file types are possible to export.
2.
Configure horizontal and vertical communication in the IET600 station
configuration tool.
3.
Import SCL files to PCM600 project. In the scenario in
updated SCD file.
SCD file
PCM600 (1)
 
do IED engineering
 
export SCD file
IEC11000264 V1 EN
Figure 54:
IEC 61850: Signal engineering procedure flow

Exporting SCL files from PCM600

A pre-condition is that all IEDs in the project must be engineered in PCM600. The
hardware interface, for example the communication port, has to be selected and
configured. The used interface addresses have to be set according to protocol and
project definitions. The station communication port has to be activated in the IED,
that is to set the IEC61850-8-1Operation setting to On.
IEC 61850 communication engineering
IET600 (2)
 
create project
 
import SCD file
 
configure data sets
 
configure Report CBs
 
configure GOOSE CBs
export SCD file
 
 
 
 
IED 1
Section 7
Figure 54
when a complete station
Figure 54
it is a SCD file.
Figure 54
SCD file
PCM600 (3)
import SCD file
link GOOSE input data
Write to IED
IED 2
IED n-1
it is the
IED n
IEC11000264.vsd
73

Advertisement

Table of Contents
loading

Table of Contents