Section 7
IEC 61850 communication engineering
78
5.1. Make connections between the signals that the server is sending and the
GOOSE receive interface function blocks (GOOSEBINRCV and
GOOSEINTLKRCV) on the client's side.
If a client is defined for GOOSE receive then at least one cross
in SMT is required to be able to write the configuration to the
IED.
Be sure to set the setting Operation for GOOSEBINRCV and
GOOSEINTLKRCV to On in PST to enable GOOSE
communication.
6.
Write the configuration to the IED, see
Note that the engineered data is written to the IED when
executing a common Write to IED operation.
1MRK511240-UEN B
Figure
60.
Engineering Manual
670 series