Iec 61850 Naming Conventions To Identify An Ied - ABB Relion 670 series Engineering Manual

Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

1MRK511240-UEN B
4.5.1
670 series
Engineering Manual
IEC09000710 V1 EN
Figure 12:
PCM600: Set up a plant structure
Once a plant structure is built the name of each level in the structure should be
renamed by the names/identifications used in the grid. Use the right mouse button
to build the plant structure by selecting the elements from the context menu.
Rename the level after insertion, using the Rename possibility or the Object
Properties.
Figure 12
shows the start of a project with two IEDs placed but still not
renamed.
To build a plant structure is useful when a complete grid with an
essential number of IEDs has to be built.
Procedure to build a plant structure:
Right-click in the plant structure and select New and Create from Template ...,
or
Right-click in the plant structure and select New, General and select one of the
elements IED Group or Substation.
Click View in the menu bar and select Object Types. Select the needed
elements and drag and drop them into the plant structure. Close the window if
it does not close automatically.

IEC 61850 naming conventions to identify an IED

This section is only valid when the IEC 61850 standard is used for station bus
communication. According to the IEC 61850–6 clause 8.4, the SCL model allows
two kinds of project designation in the object properties.
A technical key is used on engineering drawings and for signal identifications.
This is contained in the attribute name as identification of each object. If this
Section 4
Setting up a project
IEC09000710-1-en.vsd