1MRK511240-UEN B
4.3
670 series
Engineering Manual
IEC09000393 V2 EN
Figure 5:
Connectivity package manager window
PCM600 recognizes the installed Connectivity Package(s) during startup and
corresponding IED types are available in PCM600 when starting a new project.
Setting up communication between PCM600 and
the IED
The communication between the IED and PCM600 is independent of the
communication protocol used within the substation or to the NCC.
The communication media is always Ethernet and the used protocol is TCP/IP.
Each IED has an RJ-45 Ethernet interface connector on the front. The front
Ethernet connector shall be used for communication with PCM600.
When an Ethernet-based station protocol is used, PCM600 communication can use
the same Ethernet port and IP address.
To connect PCM600 to the IED, two basic variants must be considered.
Direct point-to-point link between PCM600 and the IED front port. The front
port can be seen as a service port.
Indirect link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to
enable communication.
The communication procedures are the same in both cases.
1.
If needed, set the IP address for the IEDs.
2.
Set up the PC or workstation for a direct link (point-to-point), or
3.
Connect the PC or workstation to the LAN/WAN network.
4.
Configure the IED IP addresses in the PCM600 project for each IED to match
the IP addresses of the physical IEDs.
Section 4
Setting up a project
IEC09000393-2-en.vsd
19