Preset Jog Speed; Preset Speed - Rockwell Automation PowerFlex 7000 Technical Data Manual

Medium voltage ac drive
Hide thumbs Also See for PowerFlex 7000:
Table of Contents

Advertisement

Preset Jog Speed [Preset Jog Speed]
Linear Number:
40
Default Value:
6.0 Hz
Minimum Value:
1.0 Hz
Maximum Value:
60.0 Hz
Access Level:
Basic
Read/Write:
Read/Write
This parameter specifies the preset jog speed command, which is selected by the parameter Speed Ref
Select (7).
Preset Speed 1 [Preset Speed 1]
Linear Number:
33
Default Value:
30.0 Hz
Minimum Value:
0.5 Hz
Maximum Value:
75.0 Hz
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the preset speed 1 command which is selected by the parameter Speed Ref
Select (7).
Preset Speed 2 [Preset Speed 2]
Linear Number:
34
Default Value:
35.0 Hz
Minimum Value:
0.5 Hz
Maximum Value:
75.0 Hz
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the preset speed 2 command which is selected by the parameter Speed Ref
Select (7).
Preset Speed 3 [Preset Speed 3]
Linear Number:
35
Default Value:
40.0 Hz
Minimum Value:
0.5 Hz
Maximum Value:
75.0 Hz
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the preset speed 3 command which is selected by the parameter Speed Ref