5-1-2. AE-200 initial start up for a system with connection to one or more

AE-50/EW-50 controllers

Note: When connecting one or more AE-50/EW-50 controllers, make sure to make network settings for the AE-50/EW-50 first, and
then make network settings for the AE-200.
[1] Settings on the AE-50
(1) After the power is turned on to the AE-50, a language selection
screen will appear.
Select the language to be used for display, and then touch [OK].
Note: It will take approximately one minute for the display to appear
after the power is turned on.
Note: Once the initial settings have been made, [Monitor/Operation]
screen will appear after the power is turned on.
(2) The [Date and time] screen will appear.
(3) Touch the right triangle button to display the [Network] tab, and
touch it.
Referring to section 5-2-6, set the AE-50's IP address, and
then touch [Save Settings].
The AE-50 will reboot.
Note: When multiple AE-50 controllers are connected, set the IP
addresses on all AE-50.
Note: The AE-200 and AE-50's IP addresses must have the same
network address.
[2] Settings on the EW-50
(1) Refer to the Instruction Book (Initial Settings) or the EW-50 Installation Manual.
[3] Settings on the AE-200
(1) After the power is turned on to the AE-200, a language
selection screen will appear.
Select the language to be used for display, and then touch [OK].
Note: It will take approximately one minute for the display to appear
after the power is turned on.
Note: Do not touch the LCD before any settings screen appears.
Note: Once the initial settings have been made, [Monitor/Operation]
screen will appear after the power is turned on.
WT07982X03
<Reference: Default IP address)
AE-200
192.168.1.1
AE-50
192.168.1.211