(8) In the [Brightness] section, make the Show/Hide setting for the brightness/darkness status that is detected
by the built-in brightness sensor on the ME remote controller (North America: PAR-U01MEDU, Europe: PAR-
U02MEDA).
Select [Hide] not to display the brightness/darkness icons on the [Floor] or [Block] display.
Select [
] (yellow) to display the brightness icon when the brightness level in the room reaches the
predetermined brightness level.
Select [
] (gray) to display the darkness icon when the darkness level in the room reaches the
predetermined darkness level.
Select [
darkness level of the room.
Note: If the ME remote controller has no built-in brightness sensor, the brightness/darkness icons will not be displayed on the
[Floor] or [Block] display.
Note: The brightness/darkness detection thresholds are set on the ME remote controller (North America: PAR-U01MEDU,
Europe: PAR-U02MEDA)
[4] Air-conditioner Settings
(1) In the [Test run] section, select [Use] or [Do not use]. Select [Use] when performing a test run from the
operation settings screen, or when editing the electricity meter reading value on the [Measurement] display.
Editing measurement values
1. Touch the "Measurement value edit" button to open the screen below.
Note: The "Measurement value edit" button will appear only when the [Test run] setting is set to [Use].
Edit the adjusted
measurement value
2. Touch the "Edit the adjusted measurement value" button. Enter the current electricity meter reading value,
and then touch [OK].
Note: Set the setting back to [Do not use] after completing a test run.
Note: The setting will go back to [Do not use] when the time on the AE-200/AE-50 reaches 0: 00 in the morning.
Note: Only the electric energy values on the [Measurement] display will change. This setting will not affect the energy-
control-related screens.
Note: To reset the adjusted measurement value to the original cumulative value, touch the "Edit the offset value" button
and set to "0".
WT07982X03
] (yellow/gray) to display the brightness or darkness icon according to the brightness/
64
Measurement value edit
Edit the offset value

Hide quick links: