[4] Setting the contents of the schedule
(1) Touch the row of the schedule to be set in the "Contents of Schedule" section to display the schedule settings
screen.
Set the start time to apply to the schedule, set the operations to be scheduled, and then touch [OK].
Note: If [Optimized Start] is selected, the operation mode and the set temperature need to be set as well.
To copy the schedule settings between groups, see [7] below.
To copy the schedule settings between days of the week, see [5] below.
1st page (Air conditioning unit group)
Schedule settings
Scheduled start time
Note: About Optimized Start function
26ºC
• If [Optimized Start] is selected, the operation mode and the set temperature need to be set as well. The Optimized Start
function will start the units 5 to 60 minutes prior to the scheduled start time to reach the set temperature at the scheduled
start time, based on the operation data in the past. (When the units start the first time after a power reset, the units will
start operation 30 minutes before the scheduled start time.)
• [Optimized Start] can be selected only for the air conditioning unit groups.
• If the room temperature is measured by the return air temperature sensor on the air conditioning unit, the measured value
may not be an accurate representation of the temperature in the room. The temperature shown may be higher than the
actual temperature especially when the unit is stopped during the Heat mode. When this is the case, use an external
temperature sensor (PAC-SE40TSA) or remote controller sensor to measure the room temperature.
• If [Optimized Start] is selected and the [Prohibit Remote Controller] setting is set to Prohibit or Permit at the same time,
the operations from the remote controllers will be prohibited or permitted at the scheduled start time.
WT07982X03
Cool ON
Room
temperature
8:45
9:00
Operation mode: Cool
Start time: 9:00
Set temperature: 26ºC
2nd page (Air conditioning unit group)
OK
Scheduled start time
24ºC
Heat ON
8:40
Operation mode: Heat
Start time: 9:00
Set temperature: 24ºC
28
Schedule settings
Room
temperature
9:00
OK