Step - 1 Initial Setting For Air Conditioning System - Mitsubishi Electric BAC-HD150 Instruction Book

Air-conditioner control system; bm adapter
Hide thumbs Also See for BAC-HD150:
Table of Contents

Advertisement

7.3

Step - 1 Initial setting for air conditioning system

Make the initial settings for air conditioning system using Setting Tool.
Connect the
LAN2 cable.
HUB
Setting Tool
Step-1
(1) Installing the Setting Tool software
Install the Setting Tool program on a PC, and set the IP address. (Refer to the Instruction Book that came with Setting Tool for
installation and setting method.)
(2) Connecting the Setting Tool
Disconnect the LAN1 cable connected to BACnet
Use additional HUB to connect BAC-HD150 and Setting Tool.
Connect the LAN2 cable that is connected to BACnet
(3) Data setting
Make the settings for the air conditioning system related items and IP address of BAC-HD150 by using Setting Tool.
The following table shows setting items. (Refer to the Instruction Book that came with Setting Tool for setting method.)
No.
1
2
3
4
5
CAUTION
If IP address of BAC-HD150 overlaps any of the addresses that are assigned to other devices, communications
cannot be performed properly via BAC-HD150 or other devices. Check the address before setting.
MEMO :
When settings are changed by using Setting Tool after the initial settings have been completed, it is not necessary
to disconnect the LAN1 cable from BACnet
HUB
LAN1
LAN2
M-NET
BAC-HD150
System controller
®
Main tab
Basic System
System Settings
M-NET
Expansion Controller
Group
Group Settings
LOSSNAY
®
.
®
BACnet
Disconnect the
LAN1 cable.
Outdoor unit
ME remote controller
Outdoor unit
ME remote controller
of BAC-HD150.
®
to the additional HUB.
Sub tab
All setting items
All setting items
No settings required
All setting items
All setting items
- 32 -
BMS
HUB
M-NET
Indoor unit
M-NET
Indoor unit
Setting item
LOSSNAY
LOSSNAY

Advertisement

Table of Contents
loading

Table of Contents