F015
V/f Pattern
Program Fundamental Frequency Settings
This function establishes the relationship between the output frequency and the
output voltage.
Bolded selections use the motor tuning parameters of the ASD to properly
configure the ASD for the motor being used. If Load Reactors or Long Lead
Filters are used, or if the capacity of the ASD is greater than the motor, manual
tuning of the motor parameters may be required for optimum performance.
Settings:
0 — Constant Torque
1 — Variable Torque
2 — Automatic Torque Boost
3 — Sensorless Vector Control (Speed)
4 — Automatic Torque Boost + Automatic Energy Saving
5 — Sensorless Vector Control (Speed) + Automatic Energy Saving
6 — V/f 5-Point Setting (Open 5-Point Setting Window)
7 — Sensorless Vector Control (Speed/Torque Switching)
8 — PG Feedback Vector Control (Speed/Torque Switching)
9 — PG Feedback Vector Control (Speed/Position Switching)
When operating in the Vector Control mode the carrier
Note:
frequency should be set to 2.2 kHz or above
Manual Torque Boost 1
Program Fundamental Motor Set 1
The Manual Torque Boost 1 function is used to increase the low frequency
torque for high-inertia loads by increasing the output voltage at frequencies
below ½ of the Base Frequency 1 (F014) setting.
The value programmed as a boost percentage establishes an output voltage vs.
output frequency relationship to be used to start the motor or to provide
smoother operation.
Note:
Setting an excessive Torque Boost level may cause nuisance
tripping and mechanical stress to loads.
80
Direct Access Number — F015
Parameter Type — Selection List
Factory Default — Automatic Torque
Boost
Changeable During Run — No
.
Direct Access Number — F016
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
GX9 ASD Installation and Operation Manual