F230
BIN Reference Point 2
Program Frequency Speed Reference Setpoints
This parameter is used to set the speed of the BIN terminals when the BIN
terminals are used as the control input.
This parameter sets the BIN signal that is associated with BIN Input Point 2
Frequency.
This value is entered as 0% to +100% of the BIN signal range.
See BIN Reference Point 1 (F228) for further information on this setting.
BIN Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the speed of the BIN terminals when the BIN
terminal are used as the control input.
This parameter sets BIN Input Point 2 Frequency and is the frequency that is
associated with the setting of BIN Reference Point 2.
See BIN Reference Point 1 (F228) for further information on this setting.
BIN Input Point 1 Torque
Program Torque Setpoints
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input and motor load.
See
F228
for further information on this setting.
This parameter sets BIN Input Point 1 Torque and is entered as
-250 to +250% of the rated torque.
BIN Input Point 2 Torque
Program Torque Setpoints
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input and motor load.
See
F228
for further information on this setting.
This parameter sets BIN Input Point 2 Torque and is entered as
-250 to +250% of the rated torque.
GX9 ASD Installation and Operation Manual
Direct Access Number — F230
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Direct Access Number — F231
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — -Max. Freq. (F011)
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F232
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Direct Access Number — F233
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
F233
121