F440
Power Running Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting. If Setting is selected, the value set at
Power Running Torque Limit 1 input.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F441)
Power Running Torque Limit 1 Level
Program Torque Manual Torque Limit Settings
This parameter provides a value for the Power Running Torque Limit 1
setting if Setting is selected at F440. This value provides the positive torque
upper limit for the #1 motor.
Regenerative Braking Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal. If Setting is selected, the value set at
parameter.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F443)
Regenerative Braking Torque Limit 1 Level
Program Torque Manual Torque Limit Settings
This parameter provides a value to be used as the Regeneration Torque Limit
1 if Setting (F443) is selected at F442.
Power Running Torque Limit 2 Level
Program Torque Manual Torque Limit Settings
This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
GX9 ASD Installation and Operation Manual
F441
is used as the
F443
is used for this
Direct Access Number — F440
Parameter Type — Selection List
Factory Default — Setting (F441)
Changeable During Run — Yes
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F442
Parameter Type — Selection List
Factory Default — Setting (F443)
Changeable During Run — Yes
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
F444
155