Gx9 Asd Characteristics; Over-Current Protection; Gx9 Asd Capacity; Using Vector Control - Toshiba GX9 Installation & Operation Manual

Table of Contents

Advertisement

GX9 ASD Characteristics

Over-Current Protection

Each GX9 ASD model is designed for a specified operating power range. The GX9 ASD will incur a trip
if the design specifications are exceeded.
However, the GX9 ASD may be operated at 110% of the specified output-current range continuously. The
5.0 HP – 125 HP can operate at 150% for 60 seconds. The 150 HP – 1200 HP may be operated at 130%
for 120 seconds as indicated in the section titled
Prevention Level
When using the GX9 ASD for an application that controls a motor which is rated significantly less than
the maximum current rating of the GX9 ASD, the over-current limit setting will have to be changed to
match the application. See
configuration.

GX9 ASD Capacity

The GX9 ASD must not be used with a motor that has a significantly larger capacity, even if the motor is
operated under a small load. A GX9 ASD being used in this way will be susceptible to a high-output peak
current which may result in nuisance tripping.
Do not apply a level of input voltage to a GX9 ASD that is beyond that which the GX9 ASD is rated. The
input voltage may be stepped down when required with the use of a step-down transformer or some other
type of voltage reduction system.

Using Vector Control

Using Vector Control enables the system to produce very high torque over the entire operating range
even at extremely low speeds. Vector Control may be used with or without feedback. However, using
feedback increases the speed accuracy for applications requiring precise speed control. Enabling the
Automatic Energy Savings further increases the efficiency of the GX9 ASD while maintaining its robust
performance.
Vector Control is not capable of operating multiple motors connected in parallel.
See
V/f Pattern on pg. 80

Local/Remote Operation

While running in the Local mode at a non-zero speed, if the RJ45 connector is removed from the EOI, the
GX9 ASD remains in the Local mode running at the last commanded speed even though the Local LED
is off. The GX9 ASD output remains at the frequency of the Frequency Command field at the time of the
disconnect for the duration of the disconnect.
To prevent this condition, before disconnecting the RJ45 connector, ensure that the GX9 ASD is off.
14
(see F601) may be adjusted to help with nuisance over-current trips.
Motor Overload Protection Level 1
for further information on using Vector Control.
CAUTION
Voltage/Current Specifications on pg.
for further information on this ASD/motor
GX9 ASD Installation and Operation Manual
237. Also, the
Stall

Advertisement

Table of Contents
loading

Table of Contents