F412
Motor Rated Capacity (nameplate)
Program Motor Vector Motor Model
This parameter identifies the wattage rating of the motor.
Motor Type
Program Motor Vector Motor Model
This parameter identifies the type of motor being used.
Settings:
0 — Toshiba EQP III TEFC
1 — Toshiba EQP III ODP
2 — Toshiba EPACT TEFC
3 — Toshiba EPACT ODP
4 — Other Motor
Autotune of Motor Constant 3
Program Motor Vector Motor Model
This parameter Enables/Disables tuning of Motor Constant 3 during an
Autotune.
Settings:
0 — Prohibited
1 — Valid for Sensorless Vector
2 — Valid for Vector with PG
Torque Command Selection
Program Torque Torque Control
When operating in the Torque Control mode, this parameter allows the user to
select the source of the torque command signal.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — CN8 Option
6 — Binary/BCD Input
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Card
Torque Command Filter
Program Torque Torque Control
This parameter reduces the motor vibration caused by large-inertia loads. A
small value will have a great effect while an increased value will have a lesser
effect.
GX9 ASD Installation and Operation Manual
Direct Access Number — F412
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 0.10
Maximum — (ASD-Dependent)
Units — kW
Direct Access Number — F413
Parameter Type — Selection List
Factory Default — Toshiba EQP III
TEFC
Changeable During Run — No
Direct Access Number — F414
Parameter Type — Selection List
Factory Default — Valid for Sensorless
Vector
Changeable During Run — No
Direct Access Number — F420
Parameter Type — Selection List
Factory Default — RX
Changeable During Run — Yes
Direct Access Number — F421
Parameter Type — Numerical
Factory Default — 200.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 200.0
F421
151