F224
RX2 Reference Point 2
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 terminal when the
RX2 terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.
This parameter sets the RX2 level that is associated with RX2 Input Point 2
Frequency when operating in the Speed control mode or is associated with the
RX2 Input Point 2 Torque when operating in the Torque Control mode.
This value is entered as -100% to +100% of the RX2 signal range.
See RX2 Reference Point 1 (F222) for more information on this setting when
used for Speed control.
See RX2 Input Point 1 Torque (F226) for more information on this setting
when used for Torque Control.
RX2 Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 terminal when the
RX2 terminal is used as the control input while operating in the Speed Control
mode.
This parameter sets RX2 Input Point 2 Frequency and is the frequency that is
associated with the setting of RX2 Reference Point 2 when operating in the
Speed Control mode.
See RX2 Reference Point 1 (F222) for more information on this setting.
GX9 ASD Installation and Operation Manual
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100.00
Changeable During Run — Yes
Minimum — -100.00
Maximum — +100.00
Units — %
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — -Max. Freq. (F011)
Maximum — Max. Freq. (F011)
Units — Hz
F225
117