F916
Transducer Maximum Reading
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the maximum level of the transducer range for Virtual Linear
Pump operation.
Note:
The unit of measure for this parameter is selected at the
Linear Pump
Setup. The default setting is PSI.
Virtual Linear Pump Minimum
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the minimum setpoint within the Virtual Linear Pump operating
domain.
Virtual Linear Pump Maximum
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the maximum setpoint within the Virtual Linear Pump operating
domain.
Virtual Linear Pump Low Frequency Limit
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the Virtual Linear Pump Low Frequency Limit.
Virtual Linear Pump Command Source
Program Virtual Linear Pump Settings
During Direct mode or the Process Hold mode operation, this parameter sets
the Virtual Linear Pump command source.
Settings:
0 — EOI
1 — *VI/II
2 — RR
3 — Communication Option
Note:
Selecting VI/II here will result in an error message if Process
Hold is selected at F911.
210
Direct Access Number — F916
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7
Virtual
Direct Access Number — F917
Parameter Type — Numerical
Factory Default — 10.00
Changeable During Run — Yes
Minimum — 10.00
Maximum —
Direct Access Number — F918
Parameter Type — Numerical
Factory Default — 10.00
Changeable During Run — Yes
Minimum —
Maximum — 200.00
Direct Access Number — F919
Parameter Type — Numerical
Factory Default — 15.00
Changeable During Run — Yes
Minimum — 10.00
Maximum — 60.00
Units — Hz
Direct Access Number — F920
Parameter Type — Selection List
Factory Default — EOI
Changeable During Run — No
GX9 ASD Installation and Operation Manual
F920
F918
Setting
F917
Setting