F214
RR Input Point 1 Torque
Program Torque Setpoints
This parameter is used to set the gain and bias of the RR terminal when the RR
terminal is used as the control input while operating in the Torque Control
mode.
The bias and gain of the RR terminal may be trimmed at
respectively.
RR Torque Control Setup
Perform the following setup to allow the system to receive Torque Control
input at the RR terminal:
• Program Fundamental Standard Mode Selection Frequency Mode
RR.
• Program Fundamental Standard Mode Selection Command Mode
Selection Terminal Board.
• Set RR Input Point 1 Torque (F214).
• Set RR Reference Point 1 (F210) — the input analog signal level that
corresponds to the torque setting at RR Input Point 1 Torque.
• Set RR Input Point 2 Torque (F215).
• Set RR Reference Point 2 (F212) — the input analog signal level that
corresponds to the frequency setting at RR Input Point 2 Torque.
• Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR level.
Once set, as the RR voltage changes, the output torque of the ASD will vary in
accordance with the above settings.
This parameter sets RR Input Point 1 Torque and is the output torque value
that is associated with the setting of RR Reference Point 1 when operating in
the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
RR Input Point 2 Torque
Program Torque Setpoints
This parameter is used to set the gain and bias of the RR terminal when the RR
terminal is used as the control input while operating in the Torque Control
mode.
Torque Control is accomplished by establishing an associated V/f output
pattern for a given RR level.
This parameter sets RR Input Point 2 Torque and is the output torque value
that is associated with the setting of RR Reference Point 2 when operating in
the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
See RR Input Point 1 Torque (F214) for more information on this setting.
112
Direct Access Number — F214
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
F472
and F473,
Units — %
Direct Access Number — F215
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
GX9 ASD Installation and Operation Manual
F215
Torque Settings